Here are the EICR codes explained in one line each: C1 means danger present, C2 means potentially dangerous, C3 means improvement recommended, and FI means further investigation. Any C1 or C2 makes the whole report unsatisfactory, and C3 items are advisory only. FI depends on the age of the report: on reports written before the 2026 amendment to the Wiring Regulations it meant further investigation was required without delay, and it normally made the report unsatisfactory as well; on reports written to the current edition it means further investigation is advised, and does not fail the report on its own.
If you are holding an Electrical Installation Condition Report (EICR) with a list of codes on the observations page, this guide covers the typical faults behind each code and what happens next. We don’t carry out EICRs ourselves. We do the repair work a report identifies, and certify it, so the examples below are the faults we are asked to put right.
Had an EICR come back unsatisfactory? Get an estimate for the remedial work or call Mark on 07973 782 821 — based in Downend, covering Bristol and surrounding areas. No call-out charge for estimates, and no obligation.
The EICR codes explained at a glance
Every observation on the report gets one of four classification codes (EICR C1, C2, C3 or FI), grading how serious each finding is. Together they decide the overall result.
| Code | What it means | Fails the report? | What has to happen |
|---|---|---|---|
| C1 | Danger present, risk of injury | Yes | Immediate action; should be made safe on the day |
| C2 | Potentially dangerous | Yes | Urgent remedial work |
| C3 | Improvement recommended | No | Optional upgrade, worth doing but not required |
| FI | Further investigation advised (older reports: required without delay) | Not on a current report; yes on an older one | Have it investigated as soon as you can |
The table gives the rule under the current edition of the Wiring Regulations, BS 7671:2018+A4:2026. Reports written before that amendment will be in people’s files for years, so check the date on yours before you read the FI row.
The overall result sits in the summary box near the front, with coded items listed under observations. Not had the inspection yet? See what happens during an EICR, and our guide to what an EICR in Bristol involves for who needs one and when.
C1: danger present
A C1 means the inspector found something dangerous right now, with a real risk of injury. It is the most serious code, and rare in a well-kept home.
Typical C1 findings include:
- A socket or switch hanging off the wall with live terminals exposed
- A missing cover or blanking piece on the fuse board (consumer unit), leaving live parts within reach
- Metalwork that has become live because of a fault
What these have in common is that someone could touch a live part today. A connection that has overheated or scorched is a different matter: heat damage is coded C2, which is the next section.
A C1 should not simply be written down and left. Good practice is for the inspector to make it safe there and then, with your permission, even if that means isolating the circuit until it can be repaired. You should hear about it on the day, not discover it in the paperwork.
C2: potentially dangerous
A C2 means the defect was not dangerous at the moment of inspection but realistically could become so, often when a second fault occurs. So what does a C2 mean on an EICR in practice? Urgent remedial work is required, and the report is unsatisfactory until it is done.
C2 is the code we see most often on the reports people bring us. Typical examples from Bristol homes:
- No earth wire at lighting points that have metal fittings or metal switches
- Missing main protective bonding (the earth connection) to the gas or water pipework
- Scorching or heat damage around a socket, switch or fuse board connection
- No RCD (residual current device) protection on a bathroom circuit, commonly coded C2 where the circuit supplies a socket in the bathroom or where supplementary bonding is also missing. An RCD is the safety switch that trips when current leaks to earth
- Damaged cable with the coloured insulation exposed
- DIY additions joined in unenclosed connector blocks under floors or in lofts
None of these will necessarily hurt anyone today. That is the point of the code: the danger is one fault, one wet hand or one loose strand away, so the work is urgent, not optional.
One C2 on its own makes the report unsatisfactory. If that has just happened, our guide to what to do after a failed EICR walks through the next steps.
C3: improvement recommended, and no, it is not a fail
This is the code that causes the most confusion. A C3 means the installation falls short of BS 7671 (the current Wiring Regulations) in some respect, but is not dangerous. C3 items do not make the report unsatisfactory. A report with only C3 observations is a pass.
Common C3 examples:
- A plastic fuse board that is otherwise in good condition, where it sits under a wooden staircase or on the only escape route out of the home
- No RCD protection on lighting circuits
- No supplementary bonding in a bathroom where the circuits are RCD protected
- Older but serviceable sockets, switches and accessories
The regulations improve with every edition, so almost every house more than a few years old picks up a C3 or two. That is normal. The improvements are worth considering next time you have electrical work done, but a C3 places no legal duty on you.
This matters most in rented property, where landlords are sometimes told they must fix every code listed. They do not. Our guide to C2 vs C3 for landlords covers what the law requires and what is merely advice.
FI: further investigation, and why the date on the report matters
An FI means the inspection turned up something that looks wrong but could not be fully diagnosed within its scope. What it does to the overall result depends on when the report was written.
- On a report written to the current edition, BS 7671:2018+A4:2026, FI reads “further investigation is advised”. Like a C3 it is advisory, and it does not make the report unsatisfactory on its own.
- On a report written before the 2026 amendment, FI meant further investigation was required without delay, and it normally did make the result unsatisfactory.
Both kinds of report will be around for years, so check the date on yours.
Things an inspector may have marked FI on an older report include:
- A test reading, such as low insulation resistance, worse than expected with no visible cause
- A cable or circuit that could not be identified or traced
- Signs of an alteration where the inspector could not see how, or whether, it was safely connected
Current guidance from the IET is that a low insulation resistance reading or a circuit that cannot be identified should be given a code, not an FI.
Whichever edition your report was written to, an FI is not the inspector being vague; it is an honest flag that something needs tracing. Further investigation may uncover a C1 or C2 hiding behind it, so have it looked into as soon as you can. The investigation is often quick, and the cause either gets fixed or proves harmless.
Satisfactory or unsatisfactory: how the overall result works
The rule is simple. On a report written to the current edition of the Wiring Regulations, any C1 or C2 makes the overall assessment unsatisfactory. If the report contains only C3 or FI observations, or no observations at all, it is satisfactory. On a report written before the 2026 amendment, an FI normally made the result unsatisfactory as well.
For homeowners, an unsatisfactory report carries no legal deadline. C1 and C2 items are genuine safety issues though, so get an estimate and have them fixed promptly rather than filing the report away.
For landlords in England the rules are stricter. Under the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020, the remedial work an unsatisfactory report requires must be completed within 28 days starting with the date of the inspection, or sooner if the report says so, with written confirmation supplied to the tenant and the local authority. The clock runs from the inspection, not from the day the report arrives. From 30 November 2026 that duty covers remedial work only; for an inspection completed before that date it also covers any further investigation the report required. Councils can impose substantial civil penalties for a breach. The full requirements are in the GOV.UK guide for landlords, and the coding system is set out in Electrical Safety First’s best practice guide.
Getting the coded items put right
The report belongs to you, and any qualified electrician can work from it. The observations page lists each fault with its code and where it is, which is everything needed to estimate the repair.
Whoever does the work, ask for an estimate covering the items that make the report unsatisfactory, set out against the observations on the report so you can see what each item relates to. C3s should be listed separately as optional. You do not normally need a whole new EICR afterwards; a certificate for the remedial work is enough to show the defects were put right.
That is the part we do. Send us the report from any inspector and we will give you an estimate for the C1 and C2 items, and for investigating anything marked FI, before any work starts, then certify the work once it is done. Our page on remedial work after an unsatisfactory EICR explains how it works.
Frequently asked questions
What does C2 mean on an EICR?
C2 means potentially dangerous: the defect is not an immediate danger, but it could become one, often if a second fault develops. A C2 makes the report unsatisfactory, and urgent remedial work is required to put it right. Common C2s include missing main earth bonding, heat damage at connections, and a bathroom circuit with neither RCD protection nor supplementary bonding.
Is a C3 code a fail on an EICR?
No. C3 means improvement recommended, and it does not affect the overall result. A report containing only C3 observations is satisfactory. C3 items simply show where the installation falls short of the current Wiring Regulations without being dangerous, such as lighting circuits without RCD protection, or a sound plastic fuse board that sits under a wooden staircase.
How long do I have to fix C1 and C2 faults?
Landlords in England must have the remedial work completed within 28 days starting with the date of the inspection, or sooner if the report says so, and confirm it in writing to the tenant and local authority. The 28 days do not wait for the report to arrive. Homeowners face no legal deadline, but a C1 should be made safe on the day, and C2s are best dealt with promptly.
Can the same electrician fix the faults they found?
Yes, if they offer repairs, but you are free to take the report to any qualified electrician for the remedial work. Every remedial job we do starts from another inspector’s report, because we don’t carry out the inspections ourselves. We give an estimate for the coded items before starting, and agree any change with you before carrying on.
Do I need a new EICR once the faults are fixed?
Usually not. The electrician who does the repairs issues a certificate for that work, and that certificate kept with the original report shows the coded defects were put right. A fresh inspection only comes into it if a buyer, lender or letting agent specifically asks for a new satisfactory report.
Want the codes on your report sorted properly? Get an estimate for the remedial work or call Mark on 07973 782 821 — based in Downend, covering Bristol and surrounding areas. No call-out charge for estimates, and no obligation.